Heat pumps: common questions
Short answers on whether a heat pump suits your house, what it costs to run, how loud it is and what has to change before one goes in.
Works out one room's design heat loss, the figure a heat pump and its radiators are sized from.
Most of the form is filled in already with figures that give a sensible answer. Adjust what you know and press the button.
Calculate the design heat loss of a single room in watts, following BS EN 12831 as MIS 3005-D applies it. This is the figure a heat pump is sized from and the figure the radiator in that room must be able to deliver.
BS EN 12831 is a room-by-room method. Run this once for each heated room and add the results; sizing a heat pump from floor area alone is what produces the oversized installations that cycle all winter.
Internal design temperatures come from Table 1 of MIS 3005-D and follow from the room type: 22 for a bathroom, 21 for living and dining rooms, 18 for bedrooms, halls, kitchens and toilets. These are minimums, so a higher figure is accepted and a lower one is refused.
External design temperatures come from Table 2, for eight locations, in two columns: 'a' is the 99% figure and 'b' the colder 99.6% one, which needs no uplift for intermittent heating.
Each element needs an area, a U-value, and a kind. The kind matters because it fixes which temperature difference applies. Walls, windows, doors, roofs and suspended floors lose heat to the outside design temperature. A SOLID FLOOR ON THE GROUND loses heat to the local annual average air temperature instead, which is far warmer, and getting this wrong is the commonest error in a heat loss calculation. Window and door areas belong to the window and the door, not to the wall behind them.
The same calculation answers on
POST /api/calculators/room-heat-loss
and as the MCP tool room_heat_loss.
How to call them.
Short answers on whether a heat pump suits your house, what it costs to run, how loud it is and what has to change before one goes in.
The temperature a heat pump has to produce is set by the radiators it is connected to, and that temperature governs the running cost. This is how the two are related and how MCS measures the relationship.
MCS requires a heat pump to be sized from a room-by-room heat loss calculation. This is what that calculation contains, why the standard insists on it, and how to read one.
A heat pump moves heat instead of making it, which is why it can deliver more heat than the electricity it consumes. What that means for your radiators and for the way the house is heated.
A heat pump quotation should come with a room-by-room heat loss calculation. Here is what its columns mean and the handful of checks that catch most errors.